Meeting Summary - 02/27/2025 Senate Business & Commerce

Grid Monitor AI | Posted 02/28/2025

Related controls:
Keyword Tags:

▶️ - Texas Energy Fund Update - PUCT Chairman Thomas Gleeson

  • There are currently 72 applications, with 17 advancing to due diligence, representing approximately 8,900 megawatts of new generation.
  • A project by ENGIE was withdrawn due to lack of direct line of sight to necessary components, leading to its withdrawal.
  • Staff plans to present an option at the next open meeting to backfill the lost megawatts, restoring the capacity closer to the original 9,700 megawatts.
  • Three program rules from Senate Bill 2627 have been adopted, though work is ongoing on the backup power promise portion.
  • Concerns were raised about the tight timelines for projects, specifically regarding the first disbursement deadline by December.
  • Projects are expected to come online between 2026 and 2029, making current timelines challenging.
  • Chairman Gleeson suggested flexibility with project timelines, as longer timelines may avoid worthwhile projects dropping out.

▶️ - Extra High Voltage Update - PUCT Chairman Thomas Gleeson

  • ERCOT has provided two plans in response to House Bill 5066: one for existing 345kV model, another for upgrading to 765kV statewide.
  • ERCOT conducted a study with two cost scenarios: $32.99 billion for 765kV and around $30 billion for 345kV, with specific costs for the Permian region.
  • A workshop is scheduled to address uncertainties around the 765kV option, focusing on timeline, supply chain, and costs.
  • Chairman Thomas Gleeson emphasized the importance of timely execution and efficiency regardless of the voltage chosen.
  • A self-imposed deadline of May 1 is set for a decision, with defaulting to the 345kV if a consensus is not reached.
  • Concerns were raised about the reliance on extrapolated cost estimates from MISO's experience for 765kV.
  • The discussion highlighted the need for empirical scrutiny and public confidence in the decision-making process.
  • TDUs can file for using 765kV if approved by the PUC; this situation arises from provisions around regional transmission plans.
  • The committee discussed if the move to 765kV in the Permian would scale to other parts of the state.

▶️1 - SB6 King | et al.

  • Senator King introduced SB6, addressing Texas's exponential electric load growth.
  • The state's electric demand has significantly increased, requiring the grid to accommodate 50 gigawatts by 2030, up from 10 gigawatts previously estimated.
  • Businesses, especially large data centers and AI facilities, are driving this surge in electricity demand.
  • Concerns addressed include inaccurate load forecasting, the impact of large loads on the existing grid, and proper allocation of grid costs.
  • Four main challenges were identified: lack of accurate load forecasting, large loads taking existing generators offline from the ERCOT market, insufficient load-shedding protocols during emergencies, and improper allocation of grid costs.
  • Proposed solutions include improved criteria for large load interconnection processes, PUC approval for generators wanting to remove megawatts from the ERCOT market, and updated cost allocation methods.
  • The proposal advocates transparency in load forecasting, enhancing grid reliability protections, ensuring residential outage protections, and improved cost allocation.
  • A committee substitute is expected shortly.

▶️1 - Pablo Vegas, ERCOT, Invited Testimony

  • The bill provides helpful direction for managing grid reliability today and in the future.
  • Load forecasting is critical, and the bill enhances data quality for real-time and future planning.
  • Expecting a significant increase in load in the next forecast cycle.
  • The bill addresses reliability issues associated with large loads by defining three categories:
    • First category involves large loads with backup generation used as demand response during scarcity.
    • Second category offers a voluntary service program with compensation for participating in scarcity situations.
    • Third category includes non-participating large loads expected to partake in load shed events to mitigate residential and small business impacts.
  • The bill introduces a flexibility concept to better model grid risks and improve data accuracy.
  • ERCOT supports the bill and offers input and assistance to the bill authors and committee.

▶️1 - Barksdale English, PUCT, Invited Testimony

  • The bill presents both opportunities and challenges with respect to economic development and grid reliability.
  • A key focus is balancing economic opportunities with reliable grid operations.
  • Ensuring all transmission system users contribute to costs is emphasized.
  • The PUC is required to establish planning standards for new large loads.
  • Avoiding the loss of generation capacity when new large loads are added is critical.
  • The bill aims to safeguard the power supply for Texans' health and safety.

▶️1 - Senator King to Barksdale English, PUCT - PUCT Resources and Responsibilities 

  • Senator King discussed how the PUC has been assigned a significant amount of work since 2021 and has completed much of it, but still has tasks pending.
  • Concerns were raised about the ability to complete tasks such as the four CP reevaluation in a timely manner.
  • Barksdale English discussed whether additional resources are necessary to meet these demands.
  • Assurance was given that the organizational capacity and expertise have increased over time.
  • Confidence expressed in executing tasks effectively and expeditiously once approved by relevant authorities.
  • Request for 7 new full-time employees at a cost of around $1,000,000 per year to ensure timely completion.

▶️1 - Senator Schwertner to Barksdale English, PUCT - Grid Reliability Concerns

  • Senator Schwertner expressed concerns about grid reliability related to loss of generation and financial discussions between large companies and ratepayers.
  • Barksdale English confirmed that currently the PUC cannot prevent contracts that might impact grid reliability by removing large megawatts.
  • Legislation is needed for the PUC to manage the removal of large megawatts from the grid.
  • The envisioned process involves assessing the balance between new load introductions and loss of capacity to ensure grid reliability.
  • Consideration of the timing and geographic location of new generators is key to preventing negative impacts on system reliability.
  • Provisions may require resources taken offline to be available for statewide service restoration.

▶️1 - Senator Schwertner to Pablo Vegas, ERCOT - Potential Load Loss from Contractual Obligations

  • Senator Schwertner's discussion focused on the reliability and maintenance of grid operations as a primary obligation for ERCOT.
  • Addressed potential loss of large megawatts from the grid due to contractual obligations.
  • Pablo Vegas discussed a bill providing four pathways to effectively handle load loss situations.
  • One approach involves situations where a load with backup generation can disconnect from the grid to serve its own load, allowing the grid to benefit from adjacent generation capacity.
  • The bill includes provisions that allow ERCOT to require loads to use their own generators during scarcity periods.
  • ERCOT has a mechanism called 'reliability must run analysis' to evaluate the impact of generation resource loss on local transmission systems.
  • During peak periods, if generation loss poses an instability risk, mechanisms exist to require generation continuation or develop alternatives.
  • The bill particularly considers data centers, allowing their backup generation to ensure full capacity service from adjacent generation.

▶️1 - Senator Schwertner to Barksdale English, PUCT - Minimum Transmission Charges and 4CP Methodology Reevaluation

  • Senator Schwertner’s discussion on having a minimum transmission charge to address cost allocation related to large loads and new transmission.
  • Requirement to reevaluate the 4CP methodology due to potential gaming of the system.
  • Barksdale English discusses how the bill aims to ensure that large loads do not unfairly impact residential and small consumers.
  • Exploration of balancing fixed versus variable costs in transmission charges.
  • The Commission had already planned to examine this issue in the current calendar year.
  • Suggestion to combine considerations into a comprehensive directive to study transmission costs holistically.
  • Goal to achieve a nuanced understanding of minimum charges versus other cost methodologies like 4CP or 12CP.

▶️1 - Senator Schwertner King to Pablo Vegas, ERCOT - Invitation to Comment on Cost Allocation and Transmission Costs

  • ERCOT focuses on the impact from a reliability perspective.
  • Ensuring that protocols are efficient and cost-effective in achieving reliability goals.
  • Cost allocation is considered a commission issue, typically managed under PUC's purview.
  • PUC is recognized for balancing interests of various customer classes and sizes.

▶️1 - Senator Campbell to Pablo Vegas, ERCOT - Accuracy of Load Forecasts and Impact of Minimum Transmission Rate on Generation Incentive 

  • Senator Campbell inquired about the reliability of the 2029 forecast asserting a load of 150 gigawatts and if the load profile from last year's forecast remains accurate.
  • Preliminary data suggests that the future load could be significantly higher than the 150 gigawatts estimate for the 2030-2031 period.
  • ERCOT is working on tightening forecasting methods, but they currently lack improved data to validate specific forecasts.
  • Discussion included whether incentives exist for loads with backup power to contribute to grid reliability. 
  • Currently, data centers primarily use their backup for their own reliability needs.
  • The lack of participation in voluntary programs is noted.
  • Many data centers focus on using backup power solely for self-reliance during demand response scenarios.
  • Senator Campbell questioned if the minimum transmission rate acts as a disincentive for co-located generators. The answer suggests it depends on whether the load depends on the grid for service at times or not.
  • Discussion about whether loads should pay for grid services, based on their reliance on the grid, to ensure fairness.

▶️1 - Senator King - Comment

  • If a data center is completely islanded and not using the grid, they should not incur charges.
  • If connected to the grid, even for backup purposes, they should share costs.

▶️1: Senator Zaffirini to Pablo Vegas, ERCOT - Concerns of Kill Switch Provision Impacts on Grid and Public Safety

  • Senator Zaffirini asked about concerns regarding the impact of the kill switch provision on the grid and public safety.
  • Mr. Vegas responded that the kill switch provision could be beneficial for the grid by allowing more large loads to be included in a load shed scenario, thereby providing flexibility for transmission operators.
  • The provision aims to allocate the burden of load shedding more fairly across customer classes.
  • Mr. Vegas acknowledged concerns but emphasized that if managed safely, the shared burden during such events is fair.

▶️1 - Senator King - Comment

  • Some utilities currently have the capability to manually disconnect specific loads through physical means at substations.
  • There is ongoing effort to implement remote disconnection technology to manage loads more precisely.
  • The estimated cost to integrate this remote technology into a project is around $1.5 million.
  • Despite the high cost, this is seen as reasonable when compared to overall project budgets of $500 million to $1 billion.
  • Some utilities are already mandating the implementation of remote disconnection capabilities.
  • There is a push for standardization across the grid to ensure ERCOT can efficiently manage critical situations.

▶️1 - Senator Blanco to Pablo Vegas, ERCOT - Elaboration on Kill Switch Utilization Scenarios

  • Senator Blano’s discussion focused on the use of the 'kill switch' and its applications during emergency situations.
  • Pablo Vegas discusses the kill switch is an action of last resort, not used during normal operations or typical weather events.
  • Its use is considered when there is an energy emergency, specifically at EEA (Energy Emergency Alert) level three.
  • The process involves shedding load from the grid to maintain stability.
  • Transmission operators are notified quickly and must act within minutes in an emergency.
  • The approach follows a protocol based on load size, with larger operators having a higher proportion of load to shed.
  • This rapid response is essential to prevent unstable grid conditions.
  • Overall, the situation requiring the kill switch is very rare and emergent in nature.

▶️1.1 - Panel 1 - Taylor Kilroy (TPPA), Julia Harvey (TEC) , Walt Baum (Powering Texans), and Dan DiOrio (Data Center Coalition)

▶️1.1 - Julia Harvey (TEC) Testimony SB6

  • Julia Harvey testified on behalf of Texas Electric Cooperatives regarding SB6.
  • Co-ops generally support the goals of SB six, emphasizing the need for accurate load forecast validation measures.
  • Importance of building transmission suited to actual needs was highlighted.
  • Stressed the need to protect residential end users from power cuts before large, non-critical loads during load shedding.
  • Agreed with reevaluating transmission cost allocation due to potential cost shifting in current 4CP methodology.
  • Mentioned that 4CP behaviors allow some loads to pay less while still benefiting from the system.
  • Recognized reliability benefits but noted cost shifting as a consequence of the current system.
  • Discussed solutions in SB6, including the minimum transmission charge and 4CP evaluation.
  • Highlighted Sections 3 and 5 addressing load forecast and load shed issues. 

▶️1.1: Taylor Kilroy (TPPA) Testimony SB6

  • Taylor Kilroy testified on behalf of the Texas Public Power Association regarding a Senate Bill 6. 
  • TPPA represents 72 municipally owned utilities serving over 5 million Texans. 
  • TPPA broadly supports the new planning requirements for large loads in the bill. 
  • They also support the bill's goal to reassess the allocation of transmission costs.
  • There is a recommendation to move away from the 4CP methodology, as advised by the ERCOT Independent Market Monitor since 2015.
  • TPPA supports the concept of a minimum transmission charge but insists that more work is needed to avoid regulatory confusion.
  • Changing transmission cost allocation could lead to numerous rate cases, posing an administrative burden on the PUC and transmission service providers.
  • Further instructions are suggested to be included in the bill to guide PUC on implementing the new charge and adjusting utility rates.
  • Senate Bill 6 aims for fair cost distribution, potentially benefiting end-use residential customers in terms of cost and reliability.
  • TPPA believes the concerns raised can be addressed without altering the bill's original vision and intent.

▶️1.1 - Walt Baum (Powering Texans) Testimony SB6

  • Walt Baum represents Powering Texans and discusses economic growth and grid reliability in Texas.
  • Powering Texans is neutral on SB6 but agrees with many aspects of the bill.
  • Believes interconnection requirements should be strengthened for better load forecasting.
  • Supports data centers paying for grid services and using their backup generation.
  • Calls for flexible load management and re-examination of TCOS allocation methods.
  • Concerns regarding colocation with existing generators being subjected to different requirements.
  • Believes backup generation should be considered in approval processes.
  • Thinks stranded cost liability should apply both ways, with potential savings in transmission costs.

▶️1.1 - Dan DiOrio (Data Center Coalition) Testimony SB6

  • Dan Diorio from the Data Center Coalition (DCC) testified on Senate Bill 6. 
  • Expressing concerns about transmission level load shed and remote disconnect provisions without sufficient notification, which could impact public safety in Texas.
  • Data centers are crucial for services like government, hospitals, and finance, requiring constant uptime; any interruption can have significant consequences.
  • DCC suggests more stakeholder input from entities like ERCOT and PUC before deploying high-risk provisions.
  • DCC supports using backup generation during critical times with proper notification but seeks relief from environmental regulations for exceeding air permits in emergency situations.
  • Concerns include how backup generation is governed by regulations and the potential violation of these permits during emergencies.
  • DCC seeks modifications to the bill to outline proper procedures and notifications for deploying backup generation.
  • There is a need for flexibility in location of replacement generation, not restricted to the same zone, to better address generation needs such as those in the Permian Basin.
  • Data centers commonly use diesel generators due to reliability and cost, but environmental limits on usage are a concern.
  • Exploration of other backup technologies beyond diesel is ongoing, including natural gas and batteries.
  • Senators acknowledged concerns about remote disconnect and the need for collaboration to optimize backup utilization while complying with regulations.
  • Discussion on the bill's provisions related to transmission charges, interconnection costs, and the implications of colocating data centers next to power plants was raised.
  • It was noted that colocating can avoid building new transmission but involves recognizing associated interconnection cost responsibilities.

▶️1.2 - Panel 2 - Lee Bratcher (Texas Blockchain Council), Mark Bell (AECT), Warren Lasher (TxOGA), Katie Coleman (TAM)

▶️1.2: Lee Bratcher (Texas Blockchain Council) Testimony SB6

  • Supports Senate Bill 6 which aims to clear out the interconnection queue by removing phantom load.
  • Advocates for more accurate visibility into load growth through added costs for load studies.
  • Expressed concerns over uncertainty surrounding minimum transmission costs, which could slow investment.
  • Supports empowering ERCOT to shed large loads during EEA three events.
  • Unclear on whether the costs of disconnections will fall on loads, utilities, or be included in utilities' rate costs.
  • Assumes ERCOT would have discretion over flexible loads that are already 90% curtailed before EEA one events.
  • Expresses general support for the committee's efforts in SB 6 and a willingness to be a collaborative stakeholder.

▶️1.2 - Mark Bell (AECT) Testimony SB6

  • Mark Bell testified on behalf of the Association of Electric Companies of Texas regarding SB6.
  • AECT represents all segments of the electric industry, within and outside ERCOT.
  • There is high interest from large load consumers wanting to connect to the ERCOT grid.
  • Utilities have received numerous interconnection requests for the transmission system.
  • AECT supports transparency and credibility in the load forecasting process.
  • Emphasized the need to prioritize removing large loads from the grid before residential customers during an electric supply emergency.
  • Supports serving large facilities at the transmission voltage level to avoid operational challenges.
  • Endorsed the stakeholder process at the PUC and ERCOT for technical considerations.

▶️1.2 - Warren Lasher (TxOGA) Testimony SB6

  • Warren Lasher represents the Texas Oil and Gas Association, the largest aggregate consumer of electricity on the Texas grid.
  • TxOGA emphasizes the need for a reliable and cost-effective grid.
  • Concerns are raised regarding the bill's establishment of a minimum transmission charge, preferring a holistic review of transmission cost allocation first.
  • The bill should ensure the minimum transmission charge does not apply to legacy cogeneration facilities not included in utility forecasts.
  • The minimum transmission charge should not discourage new customers from co-locating resources.
  • Currently, the bill allows flexibility for the commission to set a threshold lower than 75 MW, which TxOGA believes could create uncertainty; they recommend setting 75 MW as the minimum.
  • The disconnection language could pose operational and reliability risks for large industrial facilities.

▶️1.2 - Katie Coleman (TAM) Testimony SB6

  • Katie Coleman from the Texas Association of Manufacturers mentioned the appreciation for efforts to find tailored solutions to identified problems.
  • Three main areas of concern were highlighted for refinements in the bill:
    1. Minimum Transmission Rate: Concerns about complicated implementation and suggestion to include it in the 4CP study for better handling.
    2. Disconnect Device: Call for collaborative approach and slight language modification to better capture the role of firm load shed.
    3. Backup Generation: Need for defining and bracketing backup generation to avoid impractical requirements.

▶️1.3 - Panel 3 - Michael McNamara (Lancium), Gideon Powell (Cholla Inc.), Sarah Axelrod (Crusoe), Bryn Baker (TEBA)

▶️1.3 - Michael McNamara (Lancium) Testimony SB6

  • Michael McNamara is the CEO of Lancium, an energy infrastructure technology company involved in the Stargate project in Abilene.
  • The Stargate project in Abilene is claimed to be the world's largest AI data center with 1.2 gigawatts under construction.
  • There is a plan for a large on-site battery and co-located solar facility at Stargate.
  • He stressed that transmission cost allocation should be borne by beneficiaries and highlighted the need to distinguish between new resources and co-location at existing assets.
  • Lancium supports measures to identify and differentiate legitimate new electrical loads from "phantom loads" to improve planning and efficiency.
  • McNamara mentioned concerns about potential market distortion from mandated generation deployment, particularly in relation to large loads with on-site resources during load shed events.
  • Mr. McNamara discussed concerns regarding disconnect devices for large data centers, highlighting on-site generation and battery plans to support grid reliability.
  • The Abilene data center project includes a 1,000 MW battery with 4,000 MWh capacity and natural gas backup to manage grid needs effectively.

▶️1.3 - Sarah Axelrod (Crusoe) Testimony SB6

  • Sarah Axelrod leads Public Affairs for Crusoe, a vertically integrated AI infrastructure company.
  • Crusoe’s approach involves locating data centers at sites of clean, low-cost, abundant energy, which brings investment and jobs to rural communities.
  • Crusoe aims to avoid straining the grid by using an energy-first approach, including backup power generation and on-site power build-outs.
  • Crusoe is involved in multiple Texas projects, contributing potential investments in tens of billions of dollars.
  • Recent projects like Stargate have been highlighted, and data centers are being recognized for their critical role in national security and competitiveness.
  • Crusoe advocates for a balanced approach to SB6 that incentivizes investment, ensures governance, and allows Texas to compete effectively.
  • Proposes any regulations on large loads apply across all large load customers based on capacity, regardless of their interconnection type.

▶️1.3 - Gideon Powell (Cholla Inc.) Testimony SB6

  • Gideon Powell, CEO of Cholla Inc., speaks from personal and professional perspectives.
  • Advocates for flexible load as a significant change, aligning with the vision shared by many ERCOT members.
  • Supports the initiatives outlined in Senate Bill 6.
  • Proposes a voluntary new construct for large load interconnections to address current issues and reduce friction and costs for ratepayers.
  • Emphasizes the potential benefits of inviting AI data centers and flexible loads into ERCOT's program.
  • Compares urgency and importance of energy innovation to historical events, indicating a need for leadership in AI dominance.

▶️1.3 - Bryn Baker (TEBA) Testimony SB6

  • Bryn Baker from the Texas Energy Buyers Alliance advocated for expanded transmission to meet energy needs and supported a minimum transmission fee on new loads receiving transmission level service.
  • The testimony supported reassessing cost allocation for large loads connected post-2023.
  • Emphasizing the willingness of new loads to contribute to grid costs.
  • Implementation of an economic benefit test was discussed, highlighting the need to evaluate lifetime costs and benefits with a discount factor as would be done by a CFO.
  • The importance of different voltage levels and grid enhancement through technologies like advanced conductors and software to reduce consumer costs and wiring needs was emphasized.
  • Senator Keene emphasized the importance of submitting specific language for a substitute bill by a specified deadline to aid in effective legislative crafting.
  • Discussion on flexible vs. less flexible loads, particularly concerning AI data centers, was highlighted, proposing stakeholder collaboration for mutually beneficial language.
  • The role of AI and crypto industries in grid reliability was discussed, citing Bitcoin miners as a proven example of flexible load benefiting grid stakeholders.

▶️1.4 - Panel 4 - Bill Peacock, John Crowell (Switch Data Centers), and Pat Wood (HEN)

▶️1.4 - Bill Peacock Public Testimony SB6

  • Bill Peacock testifies against SB 6, speaking on his own behalf.
  • Peacock has 20 years of experience in ERCOT related policy development.
  • He argues that SB6 continues the ineffective approach of addressing grid reliability issues caused by renewable energy over the past 15 years.
  • Peacock believes wind and solar energy are pushing the grid toward unreliability and driving thermal generation out, resulting in increased costs and grid reliability challenges.
  • Texas has attempted to solve these issues through significant market interventions: regulatory restrictions and raising electricity prices to stimulate investment in dispatchable generation.
  • Peacock points out that consumer-funded thermal energy subsidies, totaling $53 billion, have not resolved the reliability problems.
  • He suggests eliminating subsidies for both thermal and renewable energy, require wind and solar to pay their reliability costs, and remove market regulations to allow market forces to address the issues.

▶️1.4 - John Crowell (Switch Data Centers) Public Testimony SB6

  • John Kroll represents Switch Data Centers which develops, owns, and operates large data centers throughout North America.
  • Switch Data Centers currently has facilities in Houston and Austin, and is working on a major project in Texas Senate District 5.
  • Customers of Switch Data Centers include Fortune 100 companies, banks, financial institutions, social media, and national security entities.
  • Local clients in Austin include Dell Computers and the University of Texas, as well as Probabilities Electric Co-op.
  • Focused on provisions related to large load shed and environmental impacts.

▶️1.4 - Pat Wood (HEN) Public Testimony - SB6

  • Pat Wood, CEO of Hunt Energy Network, discussed the importance of on-site power solutions and dispersed on-site generation as critical for Texas.
  • Emphasis on encouraging on-site power where possible and ensuring unfettered access to the ERCOT market for all on-site generators.
  • Mentioned the importance of allowing on-site generators to be separately metered to fully participate in the market.
  • Discussed the need for reforms related to the 4CP (Coincident Peak) method, considering alternate methods like monthly or seasonal peak assessments.
  • Highlighted concerns that current transmission system fees do not adequately reflect reality and management practices could benefit from reform.
  • Emphasized the necessity to establish new rules and regulatory frameworks swiftly due to changing energy demands and potential new large loads.
  • Outlined the potential for legislating changes directly rather than deferring decisions to lengthy stakeholder processes.
  • Discussed balancing the transmission cost allocation to be fair and linked to peak usage to appropriately assign costs.

▶️1.5 - Panel 5 - Benjamin Barkley (OPUC), Wade Chappell (Kings Branch Data), and Cyrus Reed (Sierra Club)

▶️1.5 - Benjamin Barkley (OPUC) Testimony SB6

  • Benjamin Barkley, representing OPUC, served as a resource person available to answer questions.
  • Discussion centered on whether Section 2 of SB6 would benefit small consumers and ratepayers.
  • Benjamin Barkley believes the bill is favorable for small consumers and ratepayers.
  • Clarification was suggested regarding the scope of Section 2, which pertains to small commercial and residential consumers.
  • There was a mention of the minimum transmission charge, with some confusion around its intended meaning.

▶️1.5 - Wade Chappell (Kings Branch Data) Testimony SB6

  • Wade Chappell represented Kings Branch Data, a data center development company based in Fort Worth.
  • The company is focusing on developing a multibillion-dollar project targeting the AI market.
  • Their model targets smaller AI clients rather than large hyperscalers.
  • Kings Branch Data specializes in tailored services for emerging high-value AI clients.
  • They aim to provide data center infrastructure at 100 megawatt increments.
  • The company seeks to attract AI clients to Texas, facing competition from other states.
  • Their first major project is in a smaller community, expected to add over $30 million annually in local taxes.
  • Chappell emphasized the importance of regulatory frameworks for retaining smaller AI clients.
  • He underscored the benefits for smaller communities from economic opportunities due to AI investments.

▶️1.5 - Cyrus Reed (Sierra Club) Public Testimony SB6

  • Cyrus Reed emphasized the impact on residential consumers due to transmission costs.
  • Concerns are raised about how transmission costs are determined, especially related to 4CP (Four Coincident Peak).
  • Supports planning requirements and voluntary demand response services for large loads.
  • Expresses concern about co-location and suggests better reporting on new loads' energy use, location, and backup power.
  • Advocates for using new technologies like solar and storage, instead of mandating thermal dispatchable replacements.
  • Recommends lowering reporting requirements to loads as small as 25 megawatts for improved transparency and planning.

Create a free trial account: Sign Up

Grid monitor is free to try. No credit card required


Already have an account? Login

Most Active PUCT Filings

APPLICATION OF ONCOR ELECTRIC DELIVERY COMPANY LLC FOR AUTHORITY TO CHANGE RATES - (93 filings)

PROJECT TO DEVELOP COA AND SPCOA STATEWIDE AVERAGE SWITCHED ACCESS RATES FOR NOVEMBER 2025 PUBLICATION UNDER PURA § 52.155 AND 16 TAC § 26.223 - (86 filings)

BROKER REGISTRATIONS - (68 filings)

APPLICATION OF EL PASO ELECTRIC COMPANY FOR AUTHORITY TO CHANGE RATES - (50 filings)

APPLICATION OF ONCOR ELECTRIC DELIVERY COMPANY LLC TO AMEND ITS CERTIFICATE OF CONVENIENCE AND NECESSITY FOR THE DIVISION 138-KV TRANSMISSION LINE IN TARRANT AND DALLAS COUNTIES - (48 filings)

APPLICATION OF ENTERGY TEXAS, INC. TO AMEND ITS CERTIFICATE OF CONVENIENCE AND NECESSITY FOR THE SETEX AREA RELIABILITY PROJECT IN JASPER, MONTGOMERY, NEWTON, POLK, SAN JACINTO, TRINITY, TYLER, AND WALKER COUNTIES - (38 filings)

AGGREGATOR ANNUAL REPORTS - (34 filings)